CVSS 10.0 · Critical EPSS 1,0%

Kerentanan Missing Authentication for Critical Function pada honeywell iq4e firmware, honeywell iq412 firmware +3 lainnya. Skor CVSS 3.1 10.0 (Critical) menurut NVD.

Deskripsi (NVD)

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Rincian

Terbit di NVD
12 Maret 2026
Terakhir diubah
17 Juni 2026
Status NVD
Analyzed
CVSS 3.1
10.0 (Critical), sumber NVD
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H · uraikan di kalkulator
Jenis kelemahan (CWE)
CWE-306: Missing Authentication for Critical Function
EPSS (30 hari)
1,0% peluang dieksploitasi; lebih tinggi dari 62,6% CVE lain

Produk dan versi terdampak

VendorProdukVersi terdampak
honeywell iq4e firmware Semua versi sebelum 3.30
honeywell iq412 firmware Semua versi sebelum 3.30
honeywell iq422 firmware Semua versi sebelum 3.30
honeywell iq4nc firmware Semua versi sebelum 3.30
honeywell iq41x firmware Semua versi sebelum 3.30