rockwellautomation factorytalk services platform, rockwellautomation rslogix 5000, rockwellautomation studio 5000 logix designer
CVSS 9.8 · Critical KEV · sudah dieksploitasi EPSS 63,6%
Kerentanan Insufficiently Protected Credentials pada rockwellautomation factorytalk services platform, rockwellautomation rslogix 5000 +1 lainnya. Skor CVSS 3.1 9.8 (Critical) menurut NVD. Masuk katalog KEV CISA pada 5 Maret 2026, artinya sudah terbukti dieksploitasi.
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
· uraikan di kalkulator | Vendor | Produk | Versi terdampak |
|---|---|---|
| rockwellautomation | factorytalk services platform | Versi 2.10 dan sesudahnya |
| rockwellautomation | rslogix 5000 | Versi 16 hingga 20 |
| rockwellautomation | studio 5000 logix designer | Versi 21.0 dan sesudahnya |