CVSS 9.8 · Critical EPSS 2,3%
Kerentanan Missing Authentication for Critical Function pada ge rt430 firmware, ge rt431 firmware +1 lainnya. Skor CVSS 3.1 9.8 (Critical) menurut NVD.
GE Grid Solutions Reason RT Clocks, RT430, RT431, and RT434, all firmware versions prior to 08A05. The device’s vulnerability in the web application could allow multiple unauthenticated attacks that could cause serious impact. The vulnerability may allow an unauthenticated attacker to execute arbitrary commands and send a request to a specific URL that could cause the device to become unresponsive. The unauthenticated attacker may change the password of the 'configuration' user account, allowing the attacker to modify the configuration of the device via the web interface using the new password. This vulnerability may also allow an unauthenticated attacker to bypass the authentication required to configure the device and reboot the system.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
· uraikan di kalkulator | Vendor | Produk | Versi terdampak |
|---|---|---|
| ge | rt430 firmware | Semua versi sebelum 08a05 |
| ge | rt431 firmware | Semua versi sebelum 08a05 |
| ge | rt434 firmware | Semua versi sebelum 08a05 |